40% - 110% of lΔn
(goes up by 5%)
Testing time
300ms × 15steps
Accuracy
(Trip Time)
1%rdg±3dgt
1%rdg±3dgt
1%rdg±3dgt
Test Current at each step
-4%~+4%
Accuracy
(Trip Time)
+2%~+8%dgt
+2%~+8%dgt
-8%~-2%dgt
Voltage Measurement
Measuring range
80V~450V 50/60Hz
Accuracy
2%rdg±4dgt
Applicable standards
IEC 61010-1 Pollution degree2 CAT III 300V / CAT II 400V
IEC 61010-031
IEC 61557-1, 6
IEC 60529 (IP54)
Display
1999 counts (3 1/2digits), Large LCD
Operating temperature & humidity range
0ºC - 40ºC, relative humidity 85% (no condensation)
Storage temperature & humidity range
-20ºC - 60ºC, relative humidity 85% (no condensation)
Insulation resistance
50MΩ or more / 1000V (between electrical circuit and enclosure)
Sleep Function
(1)Automatically enters Sleep mode in 3 minutes after the last switch operation (current consumption 75µA). This function doesn't work at voltage measurements. To exit from the Sleep mode, set the Function switch to OFF position once, and re-set it to the Range at which a measurement to be conducted.
(2) Backlight turns off in 1 minute after it lights up.
Power source
DC 12V / Size AA battery R6 (SUM-3) × 8 pcs.
Dimensions
167(L)×186(W)×89(D)mm
Weight
Approx. 965g (including batteries)
Possible number of Measurements
1200 times or more
(measure every 30 seconds at ×1/2 Range, lΔn=100mA)
Included Accessories
7128A (Test leads)
7129A (Test lead with alligator clip)
8017 (Long pin) × 2
Cord case, 9121 (Shoulder strap), Instruction manual,
Size AA battery R6 (SUM-3) × 8pcs.
Video đang được cập nhật...!
* Quý khách đặt hàng hoặc liên hệ với nhân viên tư vấn để được mức chiết khấu tốt nhất.